The best fire rating available for the drainage stack
As part of the on-going development of Terrain drainage systems, we have developed a comprehensive range of passive fire protection products for use with Terrain PVC soil and waste, Terrain Fuze and Terrain Acoustic dB12. These products will enable secure specification of Terrain drainage systems with the confidence of conforming to the requirements of Part B Building Regulations. In addition all products comply with BS 476 Part 20 and BS EN 1366-3.
The Terrain Firetrap range comprises:
Terrain Firetrap Sleeves
- Ideal for Terrain Fuze stacks
- Up to 4 hour fire protection
- Quick to install in new build and retro-fit
- Protects compartment above and below slab
Terrain Firetrap Collars
- Suitable for all Terrain drainage systems
- Can be surface mounted or built in
- Up to 4 hour fire protection
In addition, independent testing has been carried out on both Firetrap Sleeves and Firetrap Collars in typical floor installations, full details available on page 10 of the Terrain FireTrap brochure.
Firetrap Sleeves
Terrain Firetrap Sleeve was developed with ease of installation in mind. The sleeve can be quickly and simply fitted onto the pipe and slid into the penetration ensuring that there are no air gaps around the sleeves by filling with mortar or mastic. In a fire situation the sleeve expands to fill the available space (15mm max) between the pipe and the penetration and will crush and close off plastic drainage pipes. The pipe forms a solid char preventing the passage of fire and smoke to the adjacent compartment.
Applications
Terrain Fuze, Terrain Acoustic dB12 and Terrain PVC soil and waste above ground drainage through:
- Concrete, masonry or plasterboard partitions
- Concrete floor constructions
Benefits
- Up to 4 Hour Fire Rating to BS 476 Part 20, BS EN 1366-3
- Protects pipe above and below the slab
- Cost effective
- One sleeve can replace two collars
- Easy installation
- Don't have to drill slab
- No need for mechanical fixings
- No mastic is required, providing close fit
- Easily cut to size to minimise wastage
- Simple to install without special tools or skills
- Will accept hole irregularities of up to 15mm
- Can be retro-fitted
- Offers excellent acoustic insulation
- Maintains the thermal insulation of the pipe through the slab or wall penetration
- Maintains vapour seal of existing insulation
- Allows for thermal movement of pipe
Firetrap Collars - for Terrain PVC soil and waste
Terrain Firetrap Collars (for PVC soil and waste) have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by services such as plastic pipe systems used in soil & waste.
The collars will seal pipes from 50mm to 160mm diameter and can be face fixed or set-in to a wall or ceiling structure. They are suitable for use on concrete, masonry and plasterboard partitions. They have a 2 hour fire rating and feature a tab closing device which ensures the pipe collars are quick and easy to fix in place.
Applications
For Terrain PVC soil and waste above ground drainage through:
- Concrete, masonry and plasterboard partitions
- Concrete floor constructions
Features
- 2 Hour fire rating
- Seals against smoke, toxic gases, flames and heat
- Can be surface mounted or built in
- Tab closing device means collars are easy to fix in place around pipe and rotate or slide into position
- Intumescent material is totally unaffected by water, is robust, 'non-flaking' and difficult to tear
- Stainless steel outer casing
Firetrap Collars - for Terrain Fuze and Terrain Acoustic dB12
Terrain Firetrap Collars have been specifically designed to re-instate the fire resistance of a wall or floor which has been penetrated by services such as Terrain Fuze or Terrain Acoustic dB12.
Manufactured in galvanised steel, each fire collar contains an internal lining of intumescent graphite wrapped in a polyethylene mesh. Anchoring hooks are also supplied.
The collars will seal pipes from 50mm to 315mm diameter and can be face fixed or set-in to a wall or ceiling structure. They are suitable for use on concrete, masonry and plasterboard partitions. They have a 2 hour or 4 hour fire rating and feature adjustable mounting tabs for quick and easy installation.
Applications
For Terrain Fuze and Terrain Acoustic dB12 above ground drainage through:
- Concrete, masonry or plasterboard partitions
- Concrete floor construction
- Fire-proof concrete
- Brickwork floors and walls
Features
- 2 Hour fire rating (up to 160mm)
- 4 Hour fire rating (200mm to 315mm)
- Galvanised steel outer casing
- Can be surface mounted or built in
- Adjustable mounting tabs for quick and easy installation
- Seals against smoke, toxic gases, fl ames and heat
- Significant noise insulating properties
- Can be installed in a recessed area to minimize overall dimensions